Inspection Information:
Facility Type: | Hot Tub/Therapeutic Pool (<19 sq.m) |
Inspection type: | Follow-Up |
Inspection date: | September 07, 2016 |
Follow-up Required: | No |
This facility was given a low hazard rating.
More information on hazard ratings.
Chlorine (Total) 5 |
Chlorine (Free Available) 3 |
Chlorine (Combined) |
Bromine (Free Available) 0 |
pH 7.2 |
Total Alkalinity 107 |
Total Hardness |
Temperature 32°C |
Clarity Satisfactory |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
101 | Critical Improper Water Chemistry/Water Clarity Observation: pH was too high at 8.4. Corrective Action: Operator was notified and after adjustment, pH is within range at 7.2. This is important for chlorine to stay effective as a disinfectant. |
401 | Note Violation Observation: Water level was too high. The entire opening of skimmer was covered. This inhibits filtration action of skimmer. Corrective Action: Water level was adjusted by operator immediately. Water level was lowered to the point that the it enters the skimmer opening. |
101 | Critical Improper Water Chemistry/Water Clarity Observation: pH was too high at 8.4. Corrective Action: Operator was notified and after adjustment, pH is within range at 7.2. This is important for chlorine to stay effective as a disinfectant. |
401 | Note Violation Observation: Water level was too high. The entire opening of skimmer was covered. This inhibits filtration action of skimmer. Corrective Action: Water level was adjusted by operator immediately. Water level was lowered to the point that the it enters the skimmer opening. |