Inspection Information:
Facility Type: | Swimming Pool/Waterslide (>19 sq.m) |
Inspection type: | Follow-Up |
Inspection date: | August 15, 2014 |
Follow-up Required: | Yes |
This facility was given a high hazard rating.
More information on hazard ratings.
Chlorine (Total) |
Chlorine (Free Available) 75 |
Chlorine (Combined) |
Bromine (Free Available) |
pH 8.2 |
Total Alkalinity 137 |
Total Hardness |
Temperature 27°C |
Clarity not very good |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
101 | Improper Water Chemistry/Water Clarity Observation: The chlorine levels are above 5ppm and we cannot calculate the combined chlorine level. Chlorine concentration must be above 1ppm and should not exceed 5. Too much chlorine poses chemical safety concerns. We must be above to calculate combined chlorine level. Corrective Action: Please bring us a proposal for automatic disinfection system and have it approved by our office and properly installed prior to reopening. |
101 | Improper Water Chemistry/Water Clarity Observation: The pH is 8.2. This is too high and must be maintained lower. Corrective Action: Must be maintained lower. |
101 | Improper Water Chemistry/Water Clarity Observation: Alkalinity is a little high still. Corrective Action: Adjust |
201 | Operating without a Permit Observation: The permit fees must be paid prior to re-opening. Corrective Action: |
203 | Inadequate or Lack of up-to-date Pool Safety Plan Observation: Pool Safety Plan Corrective Action: A pool safety plan must be submitted and approved by our office prior to reopening. |
303 | Improper Condition Causing Suction or Entrapment Hazard Observation: The main drain appears to be full of sand and debris. There is no main drain cover. The main drain should be pulling water through to the circulation and filtration system. It mist be clogged . Furthermore, with there being no cover, it the circulation was restored, there is an immediate entrapment and drowning risk. Corrective Action: This drain needs to be fixed and have anti-entrapment drain installed. THIS POOL MUST BE CLOSED TODAY. |
304 | Improper Cleanliness and/or Hygiene Observation: There is a build up of grime along upper tiles of pool. Corrective Action: These must be cleaned prior to re-opening. |
305 | Improper Maintenance of Pool Surface, Walkways, Floors and/or Construction Observation: There is chipping paint on the ceiling. Corrective Action: Please repair. Chips and cracks can cause further moisture damage and pose microbiological growth risk. |