Holiday Inn Express - Swimming Pool/Waterslide - Inspection Report

Inspection Information:
Facility Type:  Swimming Pool/Waterslide (>19 sq.m)
Inspection type:  Routine
Inspection date:  January 17, 2018
Follow-up Required:  Yes

This facility was given a high hazard rating.
More information on hazard ratings.

Field Tests
Chlorine (Total)
1.4
Chlorine (Free Available)
1.2
Chlorine (Combined)
Bromine (Free Available)
pH
7.3
Total Alkalinity
40
Total Hardness
Temperature
30.3
Clarity
satisfactory
Cyanuric Acid

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
101   Improper Water Chemistry/Water Clarity
Observation: Free chlorine at 1.2 ppm and total alkalinity at 40 ppm.
Corrective Action: Facility is order to close until violations are corrected. Adjust free chlorine so that it is > 1.5 ppm when temp is > than 30 degrees C. Raise total alkalnity to 80-120 ppm.