Inspection Information:
Facility Type: | Swimming Pool/Waterslide (>19 sq.m) |
Inspection type: | Follow-Up |
Inspection date: | June 14, 2010 |
Follow-up Required: | No |
This facility was given a high hazard rating.
More information on hazard ratings.
Chlorine (Total) |
Chlorine (Free Available) 5ppm |
Chlorine (Combined) |
Bromine (Free Available) |
pH >8 |
Total Alkalinity |
Total Hardness |
Temperature 22°C |
Clarity |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
401 | Critical Inadequate concentration of disinfectant Observation: FAC is about 5ppm Corrective Action: Adjust |
402 | Critical Repeat Inadequate pH controls Observation: pH is >8. Corrective Action: Adjust to maintain less than pH 7.8. |
408 | Critical Repeat Lack of required safety equipment Observation: The reaching pole is missing and the life ring rope is knotted. Corrective Action: Provide a pole and recoil the ring rope. |
417 | Inadequate maintenance of pool equipment Observation: 1. Some arrows in the circulation room are wrong. 2. The skimmers have no weirs. Corrective Action: 1. Label all pipes with contents and direction of flow. 2. Install weirs in the skimmers |