Inspection Information:
Facility Type: | Swimming Pool/Waterslide (>19 sq.m) |
Inspection type: | Follow-Up |
Inspection date: | February 23, 2015 |
Follow-up Required: | Yes |
This facility was given a moderate hazard rating.
More information on hazard ratings.
Chlorine (Total) |
Chlorine (Free Available) 0.65 |
Chlorine (Combined) |
Bromine (Free Available) |
pH 7.88 |
Total Alkalinity 119 ppm |
Total Hardness |
Temperature 28.2°C |
Clarity Clear |
Cyanuric Acid |
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
101 | Improper Water Chemistry/Water Clarity Observation: pH measured at 7.88 at the time of inspection. The maximum allowable pH is 7.8; ideal range is 7.2 - 7.4. A pH above 7.8 results in severe reduction of chlorine efficiacy. Corrective Action: Reduce pH immediately to below 7.8. Maintain as close within ideal range of 7.2 - 7.4 as possible. |
205 | Improper Monitoring of Chemical Paramaters or Safety Tests Observation: Improper chemistry indicates insufficient chemical monitoring. The automatic controllers are non-functional and so manual testing is required. Corrective Action: Test water chemistry at least twice per day. When a parameter is found outside of the acceptable range, correct immediately. Due to recurring chemical parameter issues, you are required to repair the automatic controller units within 2 weeks. |
101 | Improper Water Chemistry/Water Clarity Observation: pH measured at 7.88 at the time of inspection. The maximum allowable pH is 7.8; ideal range is 7.2 - 7.4. A pH above 7.8 results in severe reduction of chlorine efficiacy. Corrective Action: Reduce pH immediately to below 7.8. Maintain as close within ideal range of 7.2 - 7.4 as possible. |
205 | Improper Monitoring of Chemical Paramaters or Safety Tests Observation: Improper chemistry indicates insufficient chemical monitoring. The automatic controllers are non-functional and so manual testing is required. Corrective Action: Test water chemistry at least twice per day. When a parameter is found outside of the acceptable range, correct immediately. Due to recurring chemical parameter issues, you are required to repair the automatic controller units within 2 weeks. |