Facility Location:
1705 . Charlie Frontage Road
Fraser Lake, V0J 1S0
Facility Information:
Facility Type: | 15-300 Connections |
Current Hazard Rating: | Low |
This facility is currently under a Boil Water Notice
Underlying Problems: Water line leakage causing excessive flow and overloading filters and collapsing pressure tank. Filters have been bypassed to provide water for sanitation. UV and chlorine are still active but cannot provide adequate treatment | |
Steps Taken to Remedy: Property Manager informed all tenants of the notice Property manager contracted a plumbing company to excavate and locate problem. | |
Corrective Actions Remaining: Locate and repair water lines breaks Clean and disinfect filters and UV chamber Return filters to full operation Submit samples to ensure proper disinfection |
Facility Inspection History:
Click on an inspection link below to see additional details
Document Type | Details | |
Initial Inspection | 3-Jun-2022 | Low |