Facility Location:
2789 PG Pulp Mill Road
Prince George, V2N 2K3
Facility Information:
Facility Type: | 2-14 Connections |
Current Hazard Rating: | Low |
This facility is currently under a Boil Water Notice
Underlying Problems: Unsatisfactory water sample result. Treatment system isn’t functioning properly and chlorinator lines need to be replaced. | |
Steps Taken to Remedy: 1) Do not drink signage posted and alternative water source provided (bottled water) | |
Corrective Actions Remaining: 1) Treatment system and chlorinator lines need to be repaired. 2) The system must be shock chlorinated after repairs and maintenance are completed 3) The system must be tested and monitored to ensure that a residual chlorine 0.2 ppm is maintained throughout the system. 4) Two consecutive samples submitted at each sample site showing no bacterial presence in the water. Each sample must be taken at least 24 hours apart. |
Facility Inspection History:
Click on an inspection link below to see additional details
Document Type | Details | |
Routine Inspection | 31-Oct-2017 | Low |
Sample Range Report | 1-Apr-2017 to 30-Jun-2017 | |
Sample Range Report | 1-Jan-2017 to 31-Mar-2017 | |
Sample Range Report | 1-Oct-2016 to 31-Dec-2016 | |
Sample Range Report | 1-Apr-2016 to 30-Jun-2016 | |
Routine Inspection | 4-Dec-2007 | Low |
Routine Inspection | 8-Mar-2002 | Low |