Facility Location:
23 km North of Alice Arm
Regional District - Kitimat-Stikine
Facility Information:
Facility Type: | 2-14 Connections |
Current Hazard Rating: | Low |
This facility is currently under a Boil Water Notice
Underlying Problems: Immediate issue is a failed bulb in UV system. | |
Steps Taken to Remedy: The operator was requested to issue a boil water notice to the water users and disinfect the water system. | |
Corrective Actions Remaining: The water system will need to be shock-chlorinated, flushed and re-sampled. Two sets of consecutive samples collected from 24 hours apart will need to show no bacteria present. CP application needs to be submitted. New ERP must be submitted. |