Prince Rupert CWS

Facility Location:
424 3rd Avenue West
Prince Rupert, V8J 1L7

Facility Information:
Facility Type:  301-10000 Connections
Current Hazard Rating:   Moderate

This facility is currently under a Water Quality Advisory

     Underlying Problems: Provided at least 2 samples with absence of total coliform and E. coli. Advisory downgraded to a Water Quality Advisory (WQA) in consultation with the City of Prince Rupert. The WQA remains in place until they finish the capital water main replacement probably early September.
     Steps Taken to Remedy: Discussed activation of Emergency Response and Contingency Plan (ERCP) with operator. Boil water notice will be downgraded to a Water Quality Advisory; community will be notified.
     Corrective Actions Remaining: Complete capital water main replacement. Disinfect and flush any infrastructure repairs or replacements. Submit two satisfactory bacteriological water samples taken at least 24hrs apart, showing absence of coliforms and E.coli, from any impacted sections within the distributions system. Upon receipt of results consult with an Environmental Health Officer or Medical Health Officer prior to removal of the water quality advisory.

Facility Inspection History:
Click on an inspection link below to see additional details

Document Type   Details
Sample Range Report  1-Jan-2022 to 31-Dec-2022
Sample Range Report  1-Jan-2021 to 2-Dec-2022
Sample Range Report  1-Jan-2022 to 18-Nov-2022
Sample Range Report  28-Mar-2021 to 28-Mar-2022
Routine Inspection  28-Mar-2022  Moderate
Sample Range Report  1-Feb-2022 to 28-Feb-2022
Sample Range Report  1-Jan-2021 to 1-Jan-2022
Routine Inspection  2-Oct-2020  Moderate
Routine Inspection  12-Sep-2019  Moderate
Routine Inspection  24-Jul-2018  Low
Routine Inspection  8-Feb-2017  Low
Routine Inspection  22-Jan-2014  Low
Routine Inspection  12-Jul-2012  Low
Routine Inspection  9-Nov-2010  Low
Routine Inspection  6-Nov-2009  Low
Routine Inspection  13-May-2009  Low
Routine Inspection  6-Oct-2005  Low
Routine Inspection  25-Jun-2004  Low
Routine Inspection  7-Apr-2004  Low
Routine Inspection  26-Nov-2003  Low
Routine Inspection  11-Oct-2000  Low