Chubb Lake Bible Camp 2

Facility Location:
10295 Chubb Lake Road
Hixon, V0K 1S1

Facility Information:
Facility Type:  2-14 Connections
Current Hazard Rating:   High

This facility is currently under a Boil Water Notice

     Underlying Problems: Unsatisfactory water sample result. Underlying cause unknown and being investigated, although it can be due to recent maintenance on their pressure tank and filters.
     Steps Taken to Remedy: 1) Operator determined recent maintenance of the pressure tank and filter could have caused the total coliform results. This is not confirmed and underlying status of the system is still unknown. 2) Operator will supply the camp with bottled water and post signage on each water outlet
     Corrective Actions Remaining: 1) Operator must determine if there has been any damage, non-functioning equipment, or failures in the water system. The operator must report the findings to the Environmental Health Officer (EHO). 2) The operator must report the status and current schematics of the water system to the EHO. 3) Operator to shock chlorinate the well. Instructions were provided. 4) Operator to resample the water after one week. The water sample must show absence of total coliforms and E.coli. Two samples are required to remove the boil water notice and they must be taken at least 24 hours apart.

Facility Inspection History:
Click on an inspection link below to see additional details

Document Type   Details
Routine Inspection  27-Jul-2022  High
Routine Inspection  24-Jun-2019  Low
Sample Range Report  1-Apr-2017 to 30-Jun-2017
Sample Range Report  1-Jan-2017 to 31-Mar-2017
Routine Inspection  15-Aug-2016  Moderate
Sample Range Report  1-Apr-2016 to 30-Jun-2016
Routine Inspection  31-Jul-2011  Low
Routine Inspection  6-Jul-2010  Low
Routine Inspection  5-Jun-2007  Low
Routine Inspection  5-Jun-2007  Low
Routine Inspection  5-Jun-2007  Low