Facility Location:
7907 Barrett Hat Road
Houston, V0J 1Z1
Facility Information:
Facility Type: | 2-14 Connections |
Current Hazard Rating: | Moderate |
This facility is currently under a Boil Water Notice
Underlying Problems: It is suspected that low turnover in the post treatment storage tank and lack of sufficient disinfectant residual to be the cause cause for coliform bacteria in the finished water. | |
Steps Taken to Remedy: 1. Directed operator to initiate Boil Water Notice protocol. | |
Corrective Actions Remaining: 1. Operator plans to add chlorine to post treatment tank and flush water system. 2. Removal of the Boil Water Notice will be considered when two consecutive samples, taken a minimum 24 hours apart, are absent for Coliform bacteria and E. coli. |
Facility Inspection History:
Click on an inspection link below to see additional details
Document Type | Details | |
Routine Inspection | 27-Jul-2021 | Moderate |
Routine Inspection | 14-Jul-2020 | Low |
Routine Inspection | 4-Jun-2019 | Low |
Sample Range Report | 1-Jan-2013 to 31-Dec-2017 | |
Sample Range Report | 1-Jul-2017 to 30-Sep-2017 | |
Sample Range Report | 1-Jan-2017 to 31-Mar-2017 | |
Sample Range Report | 1-Oct-2016 to 31-Dec-2016 | |
Routine Inspection | 23-Jul-2015 | Low |
Routine Inspection | 15-Apr-2014 | Low |
Routine Inspection | 17-Jul-2013 | Moderate |
Routine Inspection | 24-Jul-2012 | Low |
Routine Inspection | 14-May-2008 | Low |
Routine Inspection | 1-Aug-2006 | Low |
Routine Inspection | 6-Jul-2005 | Low |
Routine Inspection | 3-Jun-2005 | Low |
Routine Inspection | 1-Aug-2001 | Low |