Pineview Improvement District

Facility Location:
8555 Pooley Road
Prince George, V2N 5W3

Facility Information:
Facility Type:  301-10000 Connections
Current Hazard Rating:   Low

This facility is currently under a Water Quality Advisory

     Underlying Problems: Health Canada established a Maximum Acceptable Concentration (MAC) for manganese in drinking water of 0.12 mg/L. The Pineview Improvement District draws its water from two deep wells. Test results show that the Improvement Districts groundwater wells have between 0.554 to 0.619 mg/L of manganese; the level depends on which wells are pumping and for how long.
     Steps Taken to Remedy: The Pineview Improvement District has issued a Water Quality Advisory about the levels of manganese in its drinking water supply. The Pineview Improvement District recommends using bottled water, for preparing baby formula for infants and food or drinks for young children and for adults wishing to consider other sources of drinking water. The Pineview Improvement District tests each well as part of its Water Quality Monitoring Program.
     Corrective Actions Remaining: Notify all the water users of the high manganese level and updated water quality advisory (Completed Jan 13 2023). Determine a plan of action and work with Northern Health on the institution of treatment to lower levels below the Maximum Allowable Concentration (0.12mg/L) as prescribed by the Canadian Drinking Water Guidelines (In progress)

Facility Inspection History:
Click on an inspection link below to see additional details

Document Type   Details
Sample Range Report  1-Jan-2021 to 31-Dec-2021
Sample Range Report  1-Jan-2021 to 31-Dec-2021
Routine Inspection  3-Sep-2020  Low
Sample Range Report  1-Jul-2017 to 30-Sep-2017
Routine Inspection  21-Aug-2017  Low
Routine Inspection  3-Aug-2017  Low
Sample Range Report  1-Apr-2017 to 30-Jun-2017
Other Inspection  27-Jan-2017  Low
Other Inspection  27-Jan-2017  Low
Other Inspection  27-Jan-2017  Low
Other Inspection  27-Jan-2017  Low
Other Inspection  18-May-2016  Low
Other Inspection  18-May-2016  Low
Complaint Inspection  23-Sep-2015  Low
Complaint Inspection  23-Sep-2015  Low
Routine Inspection  28-Jun-2013  Low
Routine Inspection  19-Oct-2010  Low
Routine Inspection  29-Aug-2007  Moderate
Routine Inspection  29-Aug-2007  Moderate
Routine Inspection  29-Aug-2007  Moderate
Routine Inspection  2-Mar-2001  Low