Inspection Information:
Facility Type: | WS3 |
Inspection type: | Routine |
Inspection date: | July 23, 2006 |
Follow-up Required: | Yes |
This facility was given a moderate hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
303 | Critical Microbiological Contamination of Raw Water Supply Due To Industrial Observation: Sources of contamination were observed in the proximity of the well casing. Corrective Action: Use/storage of hazardous materials on and around the well site are potential sources of well contamination; Pentachlorophenol preserved wood, old paint cans, waste oil, cement and waste items. |
317 | Inadequate or improper construction of water works Observation: Grade is not mounded up to the well casing. Corrective Action: It is important to slope impermeable soil (clay-type soil) up to the Spring so as to prevent contaminated surface waters from reaching the Spring area and infiltrating the Spring catchment. This is a special concern during spring snowmelt or heavy rain. |
318 | Inadequate Microbiological Analysis data Observation: Regular bacteriological water sample test results are not being submitted as required. Corrective Action: Bacteriological water sample tests are required according to the Conditions of the Operating Permit. |