Chubb Lake Bible Camp #1 - Inspection Report

Inspection Information:
Facility Type:  WS3
Inspection type:  Routine
Inspection date:  July 06, 2010
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
313   Inadequate treatment
Observation: Chlorine pumped directly to line and pressure tank with no significant contact time.
Corrective Action: If this water is to be used for potable purposes I would recommend a water storage tank to provide a suitable contact time for the chlorine to work.