Inspection Information:
Facility Type: | WS2 |
Inspection type: | Routine |
Inspection date: | July 16, 2007 |
Follow-up Required: | No |
This facility was given a high hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
301 | Critical Microbiological Contamination of Raw Water Supply Due To Flood Observation: Two consecutive water sample results are positive for total coliforms. Flood waters were present in close proximity to the well. Corrective Action: Boil Water Notice is in effect. |
313 | Inadequate treatment Observation: Shallow well located in floodplain, no treatment provided. Corrective Action: A treatment/disinfection system is required. Obtain a Construction Permit from the Public Health Engineer prior to making any changes to the water system. A Construction Permit application package is attached for review. |
316 | Source unprotected and subject to contamination Observation: Well lid is not fly-tight. Corrective Action: Obtain a fly-tight well cover to help ensure pests are not able to enter into the well. |
320 | Other (specify below) Observation: Grade is not sloped up to the well. Corrective Action: Slope soil (impermeable) up to the well casing in an effort to divert surface water away from the well. |
320 | Other (specify below) Observation: Water System Operator is not certified. Corrective Action: At a minimum, the Operator of this system is required to complete the WaterSafe Course or Small Water Systems training course. Information about these courses is attached for reference. |