Glacier Gulch Water Group - Inspection Report

Inspection Information:
Facility Type:  WS3
Inspection type:  Initial
Inspection date:  November 07, 2005
Follow-up Required:  Yes

This facility was given a high hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
305  Critical Microbiological Contamination of Raw Water Supply Due To Other
Observation: Water sample results positive for fecal coliforms.
Corrective Action: A system of filtration and disinfection is required.
313   Inadequate treatment
Observation: Surface water source, no treatment provided.
Corrective Action: A system of filtration and disinfection is required.
316   Source unprotected and subject to contamination
Observation: Shallow well located in close proximity to Armstrong Creek. Water obtained from well is determined to be surface water.
Corrective Action: A system of filtration and disinfection is required.