Inspection Information:
Facility Type: | WS3 |
Inspection type: | Routine |
Inspection date: | July 06, 2021 |
Follow-up Required: | No |
This facility was given a low hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
317 | Inadequate or improper construction of water works Observation: The water system is lack of treatment to deal with reoccurence of existence of Total Coliform in the water samples due to the water stagnation in reservoirs. Corrective Action: Please design and install suitable water treatment system to achieve treatment targets. |
319 | Inadequate Chemical Analysis Data Observation: The water operating permit requires chemistry data to be submitted to Northern Health every 5 years. The last chemistry was provided in 2014. Corrective Action: Please provide new chemistry date to Northern Health. |
320 | Other (specify below) Observation: The water system should be regularly shocked with chlorine to prevent formation of biofilm and other undesirable organisms. Corrective Action: Develop a shockchlorination program that shock the whole water system (especially the reservoirs) at least twice a year and submit the plan to Northern Health. Once this plan is accepted and the water results have been satisfactory, the Boil Water Notice can thus be lifted. |