Inspection Information:
Facility Type: | WS2 |
Inspection type: | Routine |
Inspection date: | June 19, 2012 |
Follow-up Required: | No |
This facility was given a moderate hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
313 | Inadequate treatment Observation: No current treatment or disinfection on water system. Corrective Action: Water system must comply with 4-3-2-1-0 surface water guidelines. Two forms of disinfection are required in addition to pre-filtration. |