Inspection Information:
Facility Type: | WS3 |
Inspection type: | Routine |
Inspection date: | August 15, 2016 |
Follow-up Required: | No |
This facility was given a moderate hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
305 | Critical Microbiological Contamination of Raw Water Supply Due To Other Observation: The lake water used in the Camp, is not for potable use, however because it is in the plumbed water system it is possible some attendees might drink this water. The last sample sent to BCCDC failed showing significant bacterial contamination. Corrective Action: The Lake water is chlorinated but with the latest bacteriological sample it is evident that a contact chamber for the chlorine to work would be of benefit to the bacteriological quality of this water. |
319 | Inadequate Chemical Analysis Data Observation: the chlorine level was not detectable, Corrective Action: the care taker should be monitoring the chlorine level every day. |