Inspection Information:
Facility Type: | WS3 |
Inspection type: | Routine |
Inspection date: | June 25, 2012 |
Follow-up Required: | Yes |
This facility was given a low hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
313 | Inadequate treatment Observation: Existing UV system lacks features able to confirm that an adequate UV dose is being provided at all times. System originally identified as requiring upgrading or replacement to NSF Standard 55A last inspection of May 19, 2011. Corrective Action: Under a construction permit process with Northern Health, upgrade or replace the existing UV system with one that is compliant to NSF Standard 55. Works to be completed by September 1, 2012. |