Inspection Information:
Facility Type: | WS3 |
Inspection type: | Follow-Up |
Inspection date: | February 19, 2008 |
Follow-up Required: | Yes |
This facility was given a high hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
313 | Critical Inadequate treatment Observation: Water from this source is considered to be surface water, or may be affected by surface water. Corrective Action: Disinfection is required on all surface water supplies, by Section 5(2) of the Drinking Water Protection Regulations. Disinfection is required prior to seasonal start-up. Approval of disinfection treatment equipment is required from the Public Health Engineer prior to installation. In the interim, a Public Boil Water Notice is required to be posted at taps throughout the site. |
318 | Critical Inadequate Microbiological Analysis data Observation: Bacteriological sampling regime is less than required by Operating Permit. Corrective Action: Bacteriological water sample results are required according to the Conditions of the Operating Permit. |