Carrier Forest Products Fabrication/Mobile Shop - Inspection Report

Inspection Information:
Facility Type:  WS3
Inspection type:  Routine
Inspection date:  July 06, 2021
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
317  Critical Inadequate or improper construction of water works
Observation: The well cap is cracked and can cause contaminants enter the water system. The surrounding ground of the well head is level.
Corrective Action: The cracked well cap must be repaired or replaced and should be maintained intact after repairement or replacement. The surrounding ground around the wellhead must have a downward slope to prevent pooled water.
319   Inadequate Chemical Analysis Data
Observation: The water operating permit requires chemistry data to be submitted to Northern Health every 5 years. The last chemistry was provided in 2014.
Corrective Action: Please provide new chemistry date to Northern Health.
320   Other (specify below)
Observation: The water system should be regularly shocked with chlorine to prevent possible formation of biofilm.
Corrective Action: Develop a shock chlorination program that shocks the water system at least twice a year and submit the plan to Northern Health. Once this plan is accepted and the water results have been satisfactory, the Boil Water Notice can thus be lifted.