Inspection Information:
Facility Type: | WS1A |
Inspection type: | Routine |
Inspection date: | June 27, 2016 |
Follow-up Required: | No |
This facility was given a low hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
313 | Inadequate treatment Observation: The distribution system is at risk. Water pressures cannot be maintained in all situations, older infrastructure and water loss indicate potential breaks or structural integrity issues with distribution lines, and a percentage of the water lines are at or below the water table for at least a portion of the year. All of these items create increased risk for intrusion of pathogens into the distribution system. Corrective Action: A variety of options are available to address identified concerns to decrease the potential for pathogen impact on the water distribution system. Addressing ways to maintain pressure, reduce structural integrity issues and to incorporate residual disinfection will provide added security and safety for this system. It is strongly recommended that residual disinfection be incorporated to add an additional barrier to potential pathogen impact on the distributed water; especially during unexpected situations. |