Inspection Information:
Facility Type: | WS2 |
Inspection type: | Routine |
Inspection date: | May 14, 2019 |
Follow-up Required: | No |
This facility was given a low hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
316 | Source unprotected and subject to contamination Observation: The blowoff drain from well 4 was draining back into the well pit. [Public Health Significance] Water from the blow off tube can contaminate the water source. Corrective Action: Ensure that the blow off water drains outside and away from the well head. |
316 | Source unprotected and subject to contamination Observation: The cover of the pit for well 4 was observed to consist of a wooden board and cast iron lid. The wooden board is porous, permeable and of improper construction. [Public Health Significance] An improperly constructed well head cover can contaminate the water source. Corrective Action: Replace the cover with non - porous and impermeable material |