Inspection Information:
Facility Type: | WS3 |
Inspection type: | Routine |
Inspection date: | April 10, 2007 |
Follow-up Required: | No |
This facility was given a low hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
317 | Inadequate or improper construction of water works Observation: a) Grade is not mounded up to the well casing. b) The artesian well outflow is not screened. Corrective Action: a) It is important to slope impermeable soil (clay-type soil) away from the well so as to prevent contaminated surface waters from reaching the well casing and infiltrating the well. b) Please ensure that the flowing artesian outflow is screened, so as to be fly-proof at all times to reduce the risk of bacteriological and rodent contamination of the water source. |