Inspection Information:
Facility Type: | WS2 |
Inspection type: | Routine |
Inspection date: | March 22, 2011 |
Follow-up Required: | No |
This facility was given a low hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
313 | Inadequate treatment Observation: Filtration - system currently employs use of 20 mm filters which is inadequate for treating water prior to UV disinfection. Corrective Action: Immediately employ filters of at least 5 mm in size or less. Recommend putting in place coarser filters upstream (for example > 20 mm) to increase service life of the smaller filter pore sizes. |