Sunset Water System - Inspection Report

Inspection Information:
Facility Type:  WS3
Inspection type:  Routine
Inspection date:  May 29, 2019
Follow-up Required:  Yes

This facility was given a moderate hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
313   Inadequate treatment
Observation: System uses surface water source with only one form of treatment, chlorine. Treatement device is not capable of treating water to meet the provincial guidelines 4-3-2-1-0. Chlorine is not effective against Giardia spp.
Corrective Action: Please make plans to install an additional form of treatment to meet the 4-3-2-1-0 treatment objectives. Submit a construction of waterworks permit application prior to construction/installation. System remains on Boil Water Notice.
320   Other (specify below)
Observation: No Emergency Response Plan available as required by permit.
Corrective Action: Please create an emergency response plan and submit it to our office.