Inspection Information:
Facility Type: | WS3 |
Inspection type: | Routine |
Inspection date: | June 15, 2016 |
Follow-up Required: | No |
This facility was given a low hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
318 | Inadequate Microbiological Analysis data Observation: Regular bacteriological water samples are not being submitted to Northern Health. Most recent bacteriological sample submitted in 2009 Corrective Action: Bacteriological water samples are required QUARTERLY as per operating permit. If bacteriological water samples have been taken please submit results to the Environmental Health Officer |
319 | Inadequate Chemical Analysis Data Observation: No record of chemical analysis on this source Corrective Action: As per Operating Permit condition, chemical sampling is required every 5 years |
320 | Other (specify below) Observation: Emergency Response Plan not available at time of inspection Corrective Action: An up-to-date Emergency Response Plan shall be maintained and posted. Please submit an Emergency Response Plan to the Environmental Health Officer |