Inspection Information:
Facility Type: | WS2 |
Inspection type: | Routine |
Inspection date: | June 18, 2012 |
Follow-up Required: | No |
This facility was given a low hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
316 | Source unprotected and subject to contamination Observation: - Well cap/lid not locked or secured in a well house. Corrective Action: - Ensure water source is well protected from vandalism with a locked lid or locked well house. |
319 | Inadequate Chemical Analysis Data Observation: - It has been more than five years since a chemical analysis has been complied. Corrective Action: - Please sample finished water for chemical/physical parameters and metal scans by July 31, 2012. Due to high organic content in surface water source, analyses for disinfection by products such as Triholmethanes (THMs) and Halo Acetic Acids (HAAs) is recommended.To minimize creation of disinfection by-products, installing a filtration system prior to chlorination would be beneficial. |