Lucille Mountain Water Users - Inspection Report

Inspection Information:
Facility Type:  WS2
Inspection type:  Routine
Inspection date:  May 06, 2004
Follow-up Required:  No

This facility was given a high hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
313  Critical Inadequate treatment
Observation: Unprotected surface source, (dammed creek) with no disinfection of any kind.
Corrective Action: Water system needs to install a comprehensive treatment system that is effective against waterborne bacteria and parasites.
316  Critical Source unprotected and subject to contamination
Observation: Other than some limited fencing, source is accessible to wildlife and trespassers. However, source is fairly remote.
Corrective Action: Total exclusion from animal and human trespass is not possible. Water supply needs to be disinfected.