Monkman Provincial Park - Well #1 - Inspection Report

Inspection Information:
Facility Type:  WS4
Inspection type:  Routine
Inspection date:  July 18, 2017
Follow-up Required:  Yes

This facility was given a high hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
318   Inadequate Microbiological Analysis data
Observation: No sampling conducted since 2015.
Corrective Action: Ensure you submit monthly bacteriological samples while in operation as required by your drinking water permit.
319   Inadequate Chemical Analysis Data
Observation: Last chemical sample was in 1993.
Corrective Action: Submit a chemical analysis that is no older than 3 years.
320   Other (specify below)
Observation: Operator has still not completed the GUDI/GARP Screening tool as required b previous inspections.
Corrective Action: Complete the attached GUDI/GARP screening tool and submit back to Northern Health for review.
320   Other (specify below)
Observation: NO Operator training
Corrective Action: Ensure you successfully complete a small water systems training course and submit a copy of your certificate to Northern Health.
320   Other (specify below)
Observation: No Emergency Response Plan
Corrective Action: Ensure you develop and maintain an updated Emergency Response Plan. This plan is to be readily available.