Inspection Information:
Facility Type: | WS4 |
Inspection type: | Follow-Up |
Inspection date: | September 06, 2012 |
Follow-up Required: | Yes |
This facility was given a moderate hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
313 | Inadequate treatment Observation: System remains without water treatment processes capable of producing necessary quality for effective disinfection. UV system in place inadequate and in need of replacement. Corrective Action: Obtain a construction permit from Northern Health public health engineer and install works capable of producing drinking water that meets the following quality: 4 log removal of viruses, 3 log removal of protozoan cysts, less than 1 NTU turbidity and 0 E. coli. Works to be completed as soon as possible, but no longer than 45 days from Sep 6, 2012. |