Inspection Information:
Facility Type: | WS3 |
Inspection type: | Routine |
Inspection date: | October 21, 2013 |
Follow-up Required: | No |
This facility was given a moderate hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
313 | Inadequate treatment Observation: System uses surface water source with only one form of treatment. - Chlorine. Treatment device is not capable of treating water to meet the provincial guidelines 4-3-2-1-0. Chlorine is not effective against cryptosporidium and less effective against giardia spp. Corrective Action: Please make pans to install an additional form of treatment to meet the 4-3-2-1-0 treatment objectives. Submit a construction permit application prior to construction/installations. |
320 | Other (specify below) Observation: Emergency response plan not available. Corrective Action: Please create an emergency response plan and submit it to our office by December 21, 2013. An Emergency Response Plan should be available/accessible at all times. Keep one copy in pumphouse. |