Lakelse Air Hangar - Inspection Report

Inspection Information:
Facility Type:  WS3
Inspection type:  Routine
Inspection date:  May 26, 2017
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
316   Source unprotected and subject to contamination
Observation: Well cap was observed to be cracked on one side.
Corrective Action: Replacement and/or sealing of the well cap is required to prevent potential contamination of the water system. Ensure well cap is fixed by November 01, 2017. It is recommended that well be protected from all sides with a barrier to prevent damage to the well, well cap or well casing.
319   Inadequate Chemical Analysis Data
Observation: There is no record of a chemical analysis performed on this Water System.
Corrective Action: A chemical water analysis must be completed and results forwarded to the Environmental Health Officer by August 31 2017. Chemical analysis is required every 5 years as per conditions on the Operating Permit.