Liard Hotsprings Resort (FN FN Ltd.) - Inspection Report

Inspection Information:
Facility Type:  WS3
Inspection type:  Routine
Inspection date:  August 11, 2021
Follow-up Required:  Yes

This facility was given a high hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
316   Source unprotected and subject to contamination
Observation: The water well is located within 30 meters of the sewage holding tank and assumed sewage dispersal area. The sewage tank appears to be fouling, and there is a strong odour coming form it.
Corrective Action: Move or repair the sewage system so it is not a potential contamination for the water.
318   Inadequate Microbiological Analysis data
Observation: Microbiologically water samples have not been submitted for analysis since August 2020.
Corrective Action: Submit monthly samples to the lab for testing. These can be done on any week of the month.
320   Other (specify below)
Observation: The operators do not have a written emergency response plan or operational plan for the water system
Corrective Action: Create an ERP and operational plan, and submit a copy to the health unit.