Inspection Information:
Facility Type: | WS2 |
Inspection type: | Routine |
Inspection date: | June 07, 2006 |
Follow-up Required: | Yes |
This facility was given a high hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
313 | Critical Inadequate treatment Observation: a) Water from this source is considered to be surface water. Disinfection is required on surface water supplies, by Section 5(2) of the Drinking Water Protection Regulations. Corrective Action: The current Boil Water Advisory remains in effect, and appropriate signage is required to be maintained, as required by the Environmental Health Officer. A plan stating how the Boil Water Advisory will be removed by the installation of disinfection treatment equipment is required. |
318 | Inadequate Microbiological Analysis data Observation: Bacteriological sampling required minimum monthly, from locations that are representative of the distribution system, as approved by the Environmental Health Officer. Corrective Action: (no corrective action) |