Liard Hotsprings Resort (FN FN Ltd.) - Inspection Report

Inspection Information:
Facility Type:  WS3
Inspection type:  Routine
Inspection date:  May 29, 2018
Follow-up Required:  Yes

This facility was given a high hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
313   Inadequate treatment
Observation: Lack of treatment for a shallow well.
Corrective Action: Well water must be treated as it is at risk of containing pathogens
316  Critical Source unprotected and subject to contamination
Observation: Lack of a well cap.
Corrective Action: On the top of the casing should be an approved well cap. It should fit snugly so debris, insects, or small animals can’t find their way into the well system
317  Critical Inadequate or improper construction of water works
Observation: Lack of well casing stick up and well head is not graded.
Corrective Action: Well casing must have a stick up of at least 30 cm to prevent surface water or contaminants from entering the well. Well must be graded to drain water away from the well head.
313   Inadequate treatment
Observation: Lack of treatment for a shallow well.
Corrective Action: Well water must be treated as it is at risk of containing pathogens
316  Critical Source unprotected and subject to contamination
Observation: Lack of a well cap.
Corrective Action: On the top of the casing should be an approved well cap. It should fit snugly so debris, insects, or small animals can’t find their way into the well system
317  Critical Inadequate or improper construction of water works
Observation: Lack of well casing stick up and well head is not graded.
Corrective Action: Well casing must have a stick up of at least 30 cm to prevent surface water or contaminants from entering the well. Well must be graded to drain water away from the well head.