Inspection Information:
Facility Type: | WS2 |
Inspection type: | Follow-Up |
Inspection date: | November 15, 2022 |
Follow-up Required: | Yes |
This facility was given a low hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
320 | Other (specify below) Observation: Elevated level of manganese identified by routing sampling for chemical/physical parameters. Samples show manganese concentration of up to 2.0 mg/L. The maximum acceptable concentration for manganese per the Guidelines for Canadian Drinking Water Quality is 0.12 mg/L. A construction permit has been issued for installation of manganese treatment. Treatment system has been installed but is not yet effectively removing manganese from the drinking water supply. Corrective Action: Make necessary adjustments to the configuration of the treatment equipment to ensure it is functioning optimally. Submit pre- and post-treatment samples for manganese to verify treatment efficacy. |