Inspection Information:
Facility Type: | WS2 |
Inspection type: | Routine |
Inspection date: | June 29, 2009 |
Follow-up Required: | Yes |
This facility was given a high hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
305 | Critical Microbiological Contamination of Raw Water Supply Due To Other Observation: June 24 sample results received - EST 170 Total Coliforms. Corrective Action: Samples taken around Strata distribution system - 5 homes, 1 raw, 1treated at pumphouse. Free chlorine residuals throughout - Nil to trace. None detected at pumphouse. |
313 | Inadequate treatment Observation: Malfunctioning chlorine pump suspected. Corrective Action: Have maintenance provider correct/repair. Resample when deemed opertional. |
320 | Other (specify below) Observation: No record of free chlorine residuals kept - Current testing equipment inadequate due to source quality. Corrective Action: Obtain new testing equipment - digital coloimeter recommended. |