Inspection Information:
Facility Type: | WS3 |
Inspection type: | Follow-Up |
Inspection date: | September 28, 2010 |
Follow-up Required: | Yes |
This facility was given a low hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
313 | Inadequate treatment Observation: Recent water samples have shown positive results for total coliform. The water filter is a rainfresh style, with nominal 5 micron efficiency. Corrective Action: Replace the filter with an absolute filter that meets the UV bulb manufacturer's recommendations. The UV bulb was last replaced in 2007. Replace the bulb and ensure that it provides adequate radiation to disinfect the water. |