Inspection Information:
Facility Type: | WS3 |
Inspection type: | Routine |
Inspection date: | September 18, 2014 |
Follow-up Required: | No |
This facility was given a low hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
313 | Inadequate treatment Observation: Water treatment does not meet Provincial 4-3-2-1-0 Guidelines for surface water sources. Cryptosporidium and Giardea can not be adequately treated using chlorine as the only form of treatment. Corrective Action: Treatment that effectively removes/kills/inactivates Giardia and Cryptosporidium by 3 log reduction is required. System remains on Boil Water Notice. Obtain a construction permit from Northern Health before installing. |