Tyee Mobile Home Park - Inspection Report

Inspection Information:
Facility Type:  WS3
Inspection type:  Routine
Inspection date:  September 18, 2014
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
313   Inadequate treatment
Observation: Water treatment does not meet Provincial 4-3-2-1-0 Guidelines for surface water sources. Cryptosporidium and Giardea can not be adequately treated using chlorine as the only form of treatment.
Corrective Action: Treatment that effectively removes/kills/inactivates Giardia and Cryptosporidium by 3 log reduction is required. System remains on Boil Water Notice. Obtain a construction permit from Northern Health before installing.