Inspection Information:
Facility Type: | WS4 |
Inspection type: | Routine |
Inspection date: | January 12, 2021 |
Follow-up Required: | No |
This facility was given a low hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
313 | Critical Inadequate treatment Observation: Manganese level in the 2018 water chemistry report (0.54mg/L) exceeded the current Maximum Acceptable Concentration of 0.12mg/L Corrective Action: Do not use well water for drinking, brewing coffee or preparing any food. Ensure that an appropriate treatment system is installed to reduce the level of Manganese to an acceptable level. |
316 | Source unprotected and subject to contamination Observation: Surfaces around water well casing is not sloped away from the well. Corrective Action: Ensure that surface surrounding the well casing is mounded to slope away from the well to prevent standing water and snow melt seeping through and resulting in contamination. |
318 | Inadequate Microbiological Analysis data Observation: Water sample is not being submitted monthly as required. This is a repeat violation. Corrective Action: Ensure that water sample is consistently submitted for bacteriological analysis on a monthly basis. |
320 | Other (specify below) Observation: Operator does not have a WaterSafe or equivalent training. This is a repeat violation. Corrective Action: Ensure to attend a WaterSafe or equivalent training and make certificate available for review during inspection. failure to comply could result in fines. Training must be completed by February 12, 2021. |