Prespatou Store (2013) Water System - Inspection Report

Inspection Information:
Facility Type:  WS4
Inspection type:  Routine
Inspection date:  January 12, 2021
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
313  Critical Inadequate treatment
Observation: Manganese level in the 2018 water chemistry report (0.54mg/L) exceeded the current Maximum Acceptable Concentration of 0.12mg/L
Corrective Action: Do not use well water for drinking, brewing coffee or preparing any food. Ensure that an appropriate treatment system is installed to reduce the level of Manganese to an acceptable level.
316   Source unprotected and subject to contamination
Observation: Surfaces around water well casing is not sloped away from the well.
Corrective Action: Ensure that surface surrounding the well casing is mounded to slope away from the well to prevent standing water and snow melt seeping through and resulting in contamination.
318   Inadequate Microbiological Analysis data
Observation: Water sample is not being submitted monthly as required. This is a repeat violation.
Corrective Action: Ensure that water sample is consistently submitted for bacteriological analysis on a monthly basis.
320   Other (specify below)
Observation: Operator does not have a WaterSafe or equivalent training. This is a repeat violation.
Corrective Action: Ensure to attend a WaterSafe or equivalent training and make certificate available for review during inspection. failure to comply could result in fines. Training must be completed by February 12, 2021.