Inspection Information:
Facility Type: | WS4 |
Inspection type: | Routine |
Inspection date: | November 13, 2019 |
Follow-up Required: | No |
This facility was given a low hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
317 | Inadequate or improper construction of water works Observation: A new drinking water system(Cisterns) was built and is in-use without obtaining approval to build such a system and secure operating permit from Northern Health. BC's Drinking water protection act requires that no drinking water system is installed prior to receiving approval to build such a system. Corrective Action: Ensure that a water works construction permit and water system application for cisterns are submitted using the application forms emailed. |
318 | Inadequate Microbiological Analysis data Observation: Bacteriological water samples are not being submitted monthly as required. This is one of the operating permit conditions. Failure to submit samples could result in fines. Corrective Action: Ensure that water samples are submitted monthly. This must be complied with immediately |
319 | Inadequate Chemical Analysis Data Observation: Chemical analysis data is not being submitted every three years as required. The last data submitted is dated 2010. Corrective Action: Ensure that water sample is submitted for chemical analysis through an approved private laboratory. This must be complied with immediately. |