Inspection Information:
Facility Type: | WS3 |
Inspection type: | Initial |
Inspection date: | May 14, 2013 |
Follow-up Required: | Yes |
This facility was given a low hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
314 | Improper maintenance of distribution system Observation: Water line delivering water to adjacent facility (The Shack) is above ground Corrective Action: Bury or contain lines as to ensure that the line is not exposed |
317 | Inadequate or improper construction of water works Observation: Casing does not have the required 60 cm stickup Corrective Action: The stickup must be extended and surrounded/secured with a non-permable material (bentonite clay is an option) to avoid water from travelling down along the casing |
318 | Inadequate Microbiological Analysis data Observation: Regular bacteriological water sample testing has not been performed since 2012 Corrective Action: Submit a bacteriological sample in June 2013 |