Precision Welding Ltd - B - 8340 Micro Sub - Inspection Report

Inspection Information:
Facility Type:  WS4
Inspection type:  Initial
Inspection date:  July 06, 2022
Follow-up Required:  No

This facility was given a low hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
301  Critical Storage Practices
Observation: Cistern is buried and lid is flush with the ground. This can allow surface water (run-off, rainwater, etc.) to pool on top of the cistern and may allow entry into the cistern, contaminating the drinking water supply.
Corrective Action: Raise the stick-up of the cistern to approximately 2 ft. above ground. Ensure lid is secure and all entry hatches are kept closed.
307  Critical Contamination of finished water - Resevoir
Observation: Eavestrough downspout is directed into the cistern through a small opening in the lid. This is contaminating the drinking water supply with rain water collected in the eavestrough.
Corrective Action: 1. Empty, clean, and disinfect the cistern. 2. Remove the drain pipe and permanently seal the hole in the lid. Ensure all entry hatches are kept closed and properly sealed.