Decker Lake Elementary School - Inspection Report

Inspection Information:
Facility Type:  WS4
Inspection type:  Routine
Inspection date:  August 25, 2011
Follow-up Required:  Yes

This facility was given a low hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
311  Critical Other (specify below)
Observation: Inadequate disinfection of raw water due to inoperation of ozone generator, and potentially inadequate dose capable of UV unit due to low UVT.
Corrective Action: EHO advised that efforts be immediately undertaken to provide adequately treated / disinfected water prior to school opening to prevent need for Boil Water Notice continuing from last June into new school year.