Fort Telkwa RV Park - Inspection Report

Inspection Information:
Facility Type:  WS2
Inspection type:  Follow-Up
Inspection date:  August 22, 2017
Follow-up Required:  No

This facility was given a moderate hazard rating.
More information on hazard ratings.

Violations:
A summary of the violations found during the inspection are listed below.

Code   Description / Observation / Corrective Action
313   Inadequate treatment
Observation: Water source is considered ground-water under the direct influence of surface water (GUDI). Inadequate treatment for pathogenic protozoa such as giardia and cryptosporidium.
Corrective Action: Please submit a construction permit application to our office by October 31, 2017. Design brief must include general timelines for installation of components. Include specifications of new contact chamber, pump, filter, and other treatment devices.