Inspection Information:
Facility Type: | WS3 |
Inspection type: | Routine |
Inspection date: | August 23, 2016 |
Follow-up Required: | Yes |
This facility was given a low hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
318 | Inadequate Microbiological Analysis data Observation: Bacteriological sampling is not being performed as per Operating Permit. Corrective Action: As per condition on Operating Permit, Bacteriological sampling is required a week before startup each season, and minimum quarterly throughout the operating season. Please submit a sample on the next sampling dates for Dease Lake; September 12 and October 3 2016. Water sampling bottles were provided to operator. |
319 | Inadequate Chemical Analysis Data Observation: Chemical sampling is not being performed as per Operating Permit Corrective Action: As per condition on Operating Permit, Chemical sampling is required a minimum frequency of every 5 years. Most recent Chemical sample was performed on July 24, 2005. Please Submit a Chemical Analysis to by July 1 2017. |