Inspection Information:
Facility Type: | WS3 |
Inspection type: | Routine |
Inspection date: | June 26, 2019 |
Follow-up Required: | Yes |
This facility was given a moderate hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description / Observation / Corrective Action |
310 | Critical Use of Unapproved Source Observation: The Operator/Water Supplier has not submitted a Water System Application or a Construction Permit for this water system even after it was requested by previous Environmental Health Officers. Corrective Action: The Operator/Water Supplier must submit a Water System Application and an Application for Waterworks Construction Permit as required by the issued Order. |
318 | Inadequate Microbiological Analysis data Observation: Bacteriological water samples are not being submitted. Corrective Action: Bacteriological water sampling is required a week before start-up and quarterly throughout the operating season. |
319 | Inadequate Chemical Analysis Data Observation: There is no recent record of chemical analysis performed on this Water System; last chemical test was conducted in 2005. Corrective Action: Chemical analysis is required every 5 years. Operator/Water Supplier must conducted a chemical water analysis and forward the results to Northern Health. |
320 | Other (specify below) Observation: An up-to-date Emergency Response and Contingency Plan has not been submitted for this Water System. Corrective Action: An updated Emergency Response Plan should be maintained. Please submit an up-to-date Emergency Response and Contingency Plan to Northern Health. |