Inspection Information:
Facility Type: | WS3 |
Inspection type: | Routine |
Inspection date: | October 01, 2008 |
Number of critical violations: | 0 |
Number of non-critical violations: | 2 |
Follow-up Required: | No |
This facility was given a low hazard rating.
More information on hazard ratings.
Violations:
A summary of the violations found during the inspection are listed below.
Code | Description |
317 | Inadequate or improper construction of water works Observation: Well located in pit, vulnerable to surface water contamination (storm water run-off, heavy rainfalls, spring melt.) Corrective Action: Well pit needs to be backfilled and sealed appropriately around casing (to minimum 10 feet). Provide sloping of ground (with clay type dirt) up to well casing to prevent surface water infiltration of well. |
319 | Inadequate Chemical Analysis Data Observation: Last chemical/physical sample taken in 2002. Corrective Action: Please submit sample to an approved lab for chemical/physical analysis, and forward to Environmental Health. |